SIMATIC S7-1200, Analog output, SB 1232, 1 AO, +/-10 V DC (12 bit resol.) or 0-20mA (11 bit resol.)
Category: SIEMENS Simatic Control Systems
Specifications
SKU
6ES7232-4HA30-0XB0
Details
| General information | ||
| Product type designation | SB 1232, AQ 1x12 bit | |
| Input current | ||
| from backplane bus 5 V DC, typ. | 15 mA | |
| output voltage / header | ||
| supply voltage of the transmitters / header | ||
| ● Supply current, max. | 25 mA | |
| Power loss | ||
| Power loss, typ. | 1.5 W | |
| Analog inputs | ||
| Number of analog inputs | 0 | |
| Analog outputs | ||
| Number of analog outputs | 1 | |
| Cycle time (all channels) max. | Voltage: 300 μS (R), 750 μS (1 uF) Current: 600 ms (1 mH); 2 ms (10 mH) | |
| Output ranges, voltage | ||
| ● -10 V to +10 V | Yes | |
| Output ranges, current | ||
| ● 0 to 20 mA | Yes | |
| Load impedance (in rated range of output) | ||
| ● with voltage outputs, min. | 1 000 Ω | |
| ● with current outputs, max. | 600 Ω | |
| Cable length | ||
| ● shielded, max. | 100 m; shielded, twisted pair | |
| Analog value generation for the outputs | ||
| Conversion principle | Differential | |
| Integration and conversion time/resolution per channel | ||
| ● Resolution with overrange (bit including sign), max. | 12 bit | |
| Errors/accuracies | ||
| Temperature error (relative to output range), (+/-) | 25 °C ±0.5%, to 55 °C ±1% | |
| Interrupts/diagnostics/status information | ||
| Alarms | Yes | |
| Diagnostics function | Yes | |
| Diagnostics indication LED | ||
| ● for status of the outputs | Yes | |
| Standards, approvals, certificates | ||
| CE mark | Yes | |
| CSA approval | Yes | |
| UL approval | Yes | |
| cULus | Yes | |
| FM approval | Yes | |
| RCM (formerly C-TICK) | Yes | |
| KC approval | Yes | |
| Marine approval | Yes | |
| Ambient conditions | ||
| Free fall | ||
| ● Fall height, max. | 0.3 m; five times, in product package | |
| Ambient temperature during operation | ||
| ● min. | -20 °C | |
| ● max. | 60 °C | |
| ● horizontal installation, min. | -20 °C | |
| ● horizontal installation, max. | 60 °C | |
| ● vertical installation, min. | -20 °C | |
| ● vertical installation, max. | 50 °C | |
| Ambient temperature during storage/transportation | ||
| ● min. | -40 °C | |
| ● max. | 70 °C | |
| Air pressure acc. to IEC 60068-2-13 | ||
| ● Storage/transport, min. | 660 hPa | |
| ● Storage/transport, max. | 1 080 hPa | |
| Relative humidity | ||
| ● Operation at 25 ℃ without condensation, max. | 95 % | |
| Pollutant concentrations | ||
| ● SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free | |
| Mechanics/material | ||
| Enclosure material (front) | ||
| ● Plastic | Yes | |
| Dimensions | ||
| Width | 38 mm | |
| Height | 62 mm | |
| Depth | 21 mm | |
| Weights | ||
| Weight, approx. | 40 g | |
View more about SIMATIC S7-1200, Analog output, SB 1232, 1 AO, +/-10 V DC (12 bit resol.) or 0-20mA (11 bit resol.) on main site