HVAC Calculation Table~

HVAC Information


Heat Load Calculation


Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft)


Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25


CFM Calculation


Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T)


Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 →


AHU / FCU Sizing


Rule: 1 TR = 400 CFM


Duct Sizing Heat Load Calculat


Velocity Limits:


Main: 1400-1800 FPM


800 CFM @ 1000 FPM 0.8 sq.ft 14"x10"


Chilled Water Flow Rate


Formula: GPM = BTU/hr/ (500 x Delta T)


Example: 24,000 BTU/hr GPM = 4.8


Pipe Sizing


Chiller Sizing


Formula: TR = BTU/hr / 12,000


Example: 60,000 BTU/hr 5 TR


Cooling Tower Sizing


Rule:


Heat Rejection = 1.25 x Load


10 TR → Tower = 12.5 TR


Sep 06,2025