SIMATIC S7-1500, digital output module DQ 16x 230V AC/2A ST; relay 16 channels in groups of 2; 4 A per group; switching cycle counter for integrated relay
Category: SIEMENS Simatic Control Systems
Specifications
SKU
6ES7522-5HH00-0AB0
Details
| General information | ||
| Product type designation | DQ 16x 230 V AC/2 A ST (relay) | |
| HW functional status | FS01 | |
| Firmware version | V1.1.0 | |
| ● FW update possible | Yes | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| ● Isochronous mode | No | |
| ● Prioritized startup | Yes | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - | |
| ● STEP 7 configurable/integrated from version | V5.5 SP3 / - | |
| ● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 | |
| ● PROFINET from GSD version/GSD revision | V2.3 / - | |
| Operating mode | ||
| ● DQ | Yes | |
| ● DQ with energy-saving function | No | |
| ● PWM | No | |
| ● Oversampling | No | |
| ● MSO | Yes | |
| ● Integrated operating cycle counter | Yes; FW V1.1.0 or higher | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Input current | ||
| Current consumption, max. | 185 mA | |
| output voltage / header | ||
| Rated value (AC) | 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC | |
| Power | ||
| Power consumption from the backplane bus | 0.8 W | |
| Power loss | ||
| Power loss, typ. | 5 W | |
| Digital outputs | ||
| Type of digital output | Relays | |
| Number of digital outputs | 16 | |
| Current-sinking | Yes | |
| Current-sourcing | Yes | |
| Digital outputs, parameterizable | Yes | |
| Short-circuit protection | No | |
| Controlling a digital input | Yes | |
| Size of motor starters according to NEMA, max. | 5 | |
| Switching capacity of the outputs | ||
| ● on lamp load, max. | 50 W (230 V AC), 5 W (24 V DC) | |
| Output current | ||
| ● for signal "1" rated value | 2 A | |
| ● for signal "1" permissible range, min. | 10 mA; 10 V | |
| ● for signal "1" permissible range, max. | 2 A; thermal continuous current | |
| ● for signal "0" residual current, max. | 0 A | |
| Parallel switching of two outputs | ||
| ● for logic links | Yes | |
| ● for uprating | No | |
| ● for redundant control of a load | Yes | |
| Switching frequency | ||
| ● with resistive load, max. | 1 Hz | |
| ● with inductive load, max. | 0.5 Hz | |
| ● on lamp load, max. | 1 Hz | |
| Total current of the outputs | ||
| ● Current per channel, max. | 2 A; see additional description in the manual | |
| ● Current per group, max. | 4 A; see additional description in the manual | |
| ● Current per module, max. | 32 A; see additional description in the manual | |
| Relay outputs | ||
| ● Number of relay outputs | 16 | |
| ● Rated supply voltage of relay coil L+ (DC) | 24 V | |
| ● Current consumption of relays (coil current of all relays), typ. | 150 mA | |
| ● external protection for relay outputs | Miniature circuit breaker B10 / B16 | |
| ● Contact connection (internal) | No | |
| ● Number of operating cycles, max. | see additional description in the manual | |
| Switching capacity of contacts | ||
| — with inductive load, max. | 2 A; see additional description in the manual | |
| — with resistive load, max. | 2 A; see additional description in the manual | |
| Cable length | ||
| ● shielded, max. | 1 000 m | |
| ● unshielded, max. | 600 m | |
| Interrupts/diagnostics/status information | ||
| Substitute values connectable | Yes | |
| Alarms | ||
| ● Diagnostic alarm | Yes | |
| ● Maintenance interrupt | Yes | |
| Diagnoses | ||
| ● Monitoring the supply voltage | Yes | |
| ● Wire-break | No | |
| ● Short-circuit | No | |
| Diagnostics indication LED | ||
| ● RUN LED | Yes; green LED | |
| ● ERROR LED | Yes; red LED | |
| ● MAINT LED | Yes; Yellow LED | |
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green LED | |
| ● Channel status display | Yes; green LED | |
| ● for channel diagnostics | No | |
| ● for module diagnostics | Yes; red LED | |
| Potential separation | ||
| Potential separation channels | ||
| ● between the channels | No | |
| ● between the channels, in groups of | 2 | |
| ● between the channels and backplane bus | Yes | |
| ● Between the channels and load voltage L+ | Yes | |
| Permissible potential difference | ||
| between different circuits | 250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels | |
| Isolation | ||
| Isolation tested with | Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test) | |
| Standards, approvals, certificates | ||
| Siemens Eco Profile (SEP) | Siemens EcoTech | |
| Suitable for safety functions | No | |
| Suitable for safety-related tripping of standard modules | Yes; From FS02 | |
| Ecological footprint | ||
| ● environmental product declaration | Yes | |
| Global warming potential | ||
| — global warming potential, (total) [CO2 eq] | 43.8 kg | |
| — global warming potential, (during production) [CO2 eq] | 9.5 kg | |
| — global warming potential, (during operation) [CO2 eq] | 34.5 kg | |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.231 kg | |
| Highest safety class achievable for safety-related tripping of standard modules | ||
| ● Performance level according to ISO 13849-1 | PL c | |
| ● Category according to ISO 13849-1 | Cat. 2 | |
| ● SIL acc. to IEC 62061 | SIL 1 | |
| ● remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/en/view/39198632 | |
| product functions / security / header | ||
| signed firmware update | No | |
| data integrity | No | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | -25 °C; From FS02 | |
| ● horizontal installation, max. | 60 °C | |
| ● vertical installation, min. | -25 °C; From FS02 | |
| ● vertical installation, max. | 40 °C | |
| Dimensions | ||
| Width | 35 mm | |
| Height | 147 mm | |
| Depth | 129 mm | |
| Weights | ||
| Weight, approx. | 350 g | |
View more about SIMATIC S7-1500, digital output module DQ 16x 230V AC/2A ST; relay 16 channels in groups of 2; 4 A per group; switching cycle counter for integrated relay on main site