SIMATIC S7-1500, digital output module DQ 32x24V DC/0.5A HF; 32 channels in groups of 8; 4 A per group
Category: SIEMENS Simatic Control Systems
Specifications
SKU
6ES7522-1BL01-0AB0
Details
| General information | ||
| Product type designation | DQ 32x24VDC/0.5A HF | |
| HW functional status | From FS02 | |
| Firmware version | V1.1.0 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| ● Isochronous mode | Yes | |
| ● Prioritized startup | Yes | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - | |
| ● STEP 7 configurable/integrated from version | V5.5 SP3 / - | |
| ● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 | |
| ● PROFINET from GSD version/GSD revision | V2.3 / - | |
| Operating mode | ||
| ● DQ | Yes | |
| ● DQ with energy-saving function | No | |
| ● PWM | No | |
| ● Cam control (switching at comparison values) | No | |
| ● Oversampling | No | |
| ● MSO | Yes | |
| ● Integrated operating cycle counter | Yes | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes; through internal protection with 7 A per group | |
| Input current | ||
| Current consumption, max. | 60 mA | |
| output voltage / header | ||
| Rated value (DC) | 24 V | |
| Power | ||
| Power consumption from the backplane bus | 1.1 W | |
| Power loss | ||
| Power loss, typ. | 3.5 W | |
| Digital outputs | ||
| Type of digital output | Transistor | |
| Number of digital outputs | 32 | |
| Current-sourcing | Yes | |
| Digital outputs, parameterizable | Yes | |
| output type acc. to IEC 61131, type 0.5 | Yes | |
| Short-circuit protection | Yes; Clocked electronically | |
| ● Response threshold, typ. | 1 A | |
| Limitation of inductive shutdown voltage to | L+ (-53 V) | |
| Controlling a digital input | Yes | |
| Switching capacity of the outputs | ||
| ● with resistive load, max. | 0.5 A | |
| ● on lamp load, max. | 5 W | |
| Load resistance range | ||
| ● lower limit | 48 Ω | |
| ● upper limit | 12 kΩ | |
| Output voltage | ||
| ● for signal "1", min. | L+ (-0.8 V) | |
| Output current | ||
| ● for signal "1" rated value | 0.5 A | |
| ● for signal "1" permissible range, max. | 0.5 A | |
| ● for signal "0" residual current, max. | 0.5 mA | |
| Output delay with resistive load | ||
| ● "0" to "1", max. | 100 µs | |
| ● "1" to "0", max. | 500 µs | |
| Parallel switching of two outputs | ||
| ● for logic links | Yes | |
| ● for uprating | No | |
| ● for redundant control of a load | Yes | |
| Switching frequency | ||
| ● with resistive load, max. | 100 Hz | |
| ● with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 | |
| ● on lamp load, max. | 10 Hz | |
| Total current of the outputs | ||
| ● Current per channel, max. | 0.5 A; see additional description in the manual | |
| ● Current per group, max. | 4 A; see additional description in the manual | |
| ● Current per module, max. | 16 A; see additional description in the manual | |
| Cable length | ||
| ● shielded, max. | 1 000 m | |
| ● unshielded, max. | 600 m | |
| Isochronous mode | ||
| Execution and activation time (TCO), min. | 70 µs | |
| Bus cycle time (TDP), min. | 250 µs | |
| Interrupts/diagnostics/status information | ||
| Diagnostics function | Yes | |
| Substitute values connectable | Yes | |
| Alarms | ||
| ● Diagnostic alarm | Yes | |
| ● Maintenance interrupt | Yes | |
| Diagnoses | ||
| ● Monitoring the supply voltage | Yes | |
| ● Wire-break | Yes | |
| ● Short-circuit | Yes | |
| ● Group error | Yes | |
| Diagnostics indication LED | ||
| ● RUN LED | Yes; green LED | |
| ● ERROR LED | Yes; red LED | |
| ● MAINT LED | Yes; Yellow LED | |
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green LED | |
| ● Channel status display | Yes; green LED | |
| ● for channel diagnostics | Yes; red LED | |
| ● for module diagnostics | Yes; red LED | |
| Potential separation | ||
| Potential separation channels | ||
| ● between the channels | No | |
| ● between the channels, in groups of | 8 | |
| ● between the channels and backplane bus | Yes | |
| Isolation | ||
| Isolation tested with | 707 V DC (type test) | |
| Standards, approvals, certificates | ||
| Siemens Eco Profile (SEP) | Siemens EcoTech | |
| Suitable for safety functions | No | |
| Suitable for safety-related tripping of standard modules | Yes; From FS02 | |
| Ecological footprint | ||
| ● environmental product declaration | Yes | |
| Global warming potential | ||
| — global warming potential, (total) [CO2 eq] | 43.8 kg | |
| — global warming potential, (during production) [CO2 eq] | 9.5 kg | |
| — global warming potential, (during operation) [CO2 eq] | 34.5 kg | |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.231 kg | |
| Highest safety class achievable for safety-related tripping of standard modules | ||
| ● Performance level according to ISO 13849-1 | PL d | |
| ● Category according to ISO 13849-1 | Cat. 3 | |
| ● SIL acc. to IEC 62061 | SIL 2 | |
| ● remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/en/view/39198632 | |
| product functions / security / header | ||
| signed firmware update | No | |
| data integrity | No | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | -30 °C; From FS03 | |
| ● horizontal installation, max. | 60 °C | |
| ● vertical installation, min. | -30 °C; From FS03 | |
| ● vertical installation, max. | 40 °C | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | |
| Dimensions | ||
| Width | 35 mm | |
| Height | 147 mm | |
| Depth | 129 mm | |
| Weights | ||
| Weight, approx. | 280 g | |
View more about SIMATIC S7-1500, digital output module DQ 32x24V DC/0.5A HF; 32 channels in groups of 8; 4 A per group on main site