| Supply voltage |
| Load voltage L+ |
| ● Rated value (DC) |
24 V |
| ● permissible range, lower limit (DC) |
20.4 V |
| ● permissible range, upper limit (DC) |
28.8 V |
| Input current |
| from load voltage L+ (without load), max. |
80 mA |
| from backplane bus 5 V DC, max. |
80 mA |
| Power loss |
| Power loss, typ. |
6.5 W |
| Digital inputs |
| Number of digital inputs |
16 |
| Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
| Number of simultaneously controllable inputs |
| horizontal installation |
| — up to 40 °C, max. |
16 |
| — up to 60 °C, max. |
8 |
| vertical installation |
| — up to 40 °C, max. |
16 |
| Input voltage |
| ● Type of input voltage |
DC |
| ● Rated value (DC) |
24 V |
| ● for signal "0" |
-30 to +5 V |
| ● for signal "1" |
13 to 30V |
| Input current |
| ● for signal "1", typ. |
7 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — at "0" to "1", min. |
1.2 ms |
| — at "0" to "1", max. |
4.8 ms |
| — at "1" to "0", min. |
1.2 ms |
| — at "1" to "0", max. |
4.8 ms |
| Cable length |
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
600 m |
| Digital outputs |
| Number of digital outputs |
16 |
| Short-circuit protection |
Yes |
| ● Response threshold, typ. |
1 A |
| Limitation of inductive shutdown voltage to |
L+ (-48 V) |
| Controlling a digital input |
Yes |
| Switching capacity of the outputs |
| ● on lamp load, max. |
5 W |
| Load resistance range |
| ● lower limit |
48 Ω |
| ● upper limit |
4 kΩ |
| Output voltage |
| ● for signal "1", min. |
L+ (-0.8 V) |
| Output current |
| ● for signal "1" rated value |
0.5 A |
| ● for signal "1" permissible range, min. |
5 mA |
| ● for signal "1" permissible range, max. |
0.6 A |
| ● for signal "1" minimum load current |
5 mA |
| ● for signal "0" residual current, max. |
0.5 mA |
| Output delay with resistive load |
| ● "0" to "1", max. |
100 µs |
| ● "1" to "0", max. |
500 µs |
| Parallel switching of two outputs |
| ● for uprating |
No |
| ● for redundant control of a load |
Yes; only outputs of the same group |
| Switching frequency |
| ● with resistive load, max. |
100 Hz |
| ● with inductive load, max. |
0.5 Hz |
| ● on lamp load, max. |
100 Hz |
| Total current of the outputs (per group) |
| horizontal installation |
| — up to 40 °C, max. |
4 A |
| — up to 60 °C, max. |
3 A |
| vertical installation |
| — up to 40 °C, max. |
2 A |
| Cable length |
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
600 m |
| Encoder |
| Connectable encoders |
| ● 2-wire sensor |
Yes |
| — permissible quiescent current (2-wire sensor), max. |
1.5 mA |
| Interrupts/diagnostics/status information |
| Alarms |
No |
| Diagnostics function |
No |
| Diagnostics indication LED |
| ● Status indicator digital input (green) |
Yes |
| ● Status indicator digital output (green) |
Yes |
| Potential separation |
| Potential separation digital inputs |
| ● between the channels |
Yes |
| ● between the channels, in groups of |
16 |
| ● between the channels and backplane bus |
Yes; Optocoupler |
| Potential separation digital outputs |
| ● between the channels |
Yes |
| ● between the channels, in groups of |
8 |
| ● between the channels and backplane bus |
Yes; Optocoupler |
| Isolation |
| Isolation tested with |
500 V DC |
| connection method |
| required front connector |
40-pin |
| Dimensions |
| Width |
40 mm |
| Height |
125 mm |
| Depth |
120 mm |
| Weights |
| Weight, approx. |
260 g |
| Classifications |
| |
| |
Version |
Classification |
| eClass |
14 |
27-24-22-04 |
| eClass |
12 |
27-24-22-04 |
| eClass |
9.1 |
27-24-22-04 |
| eClass |
9 |
27-24-22-04 |
| eClass |
8 |
27-24-22-04 |
| eClass |
7.1 |
27-24-22-04 |
| eClass |
6 |
27-24-22-04 |
| ETIM |
10 |
EC001419 |
| ETIM |
9 |
EC001419 |
| ETIM |
8 |
EC001419 |
| ETIM |
7 |
EC001419 |
| IDEA |
4 |
3566 |
| UNSPSC |
15 |
32-15-17-05 |
|
| Approvals / Certificates |
| General Product Approval |
|
Manufacturer Declaration
|

|

|
Miscellaneous
|

|

|
| EMV |
For use in hazardous locations |
|

|

|

|

|
FM
|

|
| For use in hazardous locations |
Maritime application |
|

|
Miscellaneous
|

|
CCC-Ex
|

|

|
| Maritime application |
|

|
NK / Nippon Kaiji Kyokai
|

|

|
CCS (China Classification Society)
|
|
|