Contactor AC 230 V 50 HZ AC3 4 kW 400 V AUX contacts 1 NO +1 NC 3-pole, size S0 screw terminal
Category: SIEMENS Simatic Control Systems
Specifications
SKU
3RT6023-1AP00
Details
| product brand name | SIRIUS | |
| product designation | Power contactor | |
| product type designation | 3RT6 | |
| General technical data | ||
| size of contactor | S0 | |
| product extension auxiliary switch | Yes | |
| power loss [W] for rated value of the current | ||
| ● at AC in hot operating state per pole | 0.4 W | |
| ● without load current share typical | 1.9 W | |
| type of calculation of power loss depending on pole | quadratic | |
| insulation voltage rated value | 690 V | |
| degree of pollution | 3 | |
| surge voltage resistance rated value | 6 kV | |
| maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1 | 400 V | |
| shock resistance at rectangular impulse | ||
| ● at AC | 7,5g / 5 ms, 4,7g / 10 ms | |
| shock resistance with sine pulse | ||
| ● at AC | 11,8g / 5 ms, 7,4g / 10 ms | |
| mechanical service life (operating cycles) | ||
| ● of contactor typical | 10 000 000 | |
| ● of the contactor with added auxiliary switch block typical | 10 000 000 | |
| Substance Prohibitance (Date) | 05/01/2012 | |
| Weight | 0.39 kg | |
| Ambient conditions | ||
| installation altitude at height above sea level maximum | 2 000 m | |
| ambient temperature | ||
| ● during operation | -25 ... +60 °C | |
| ● during storage | -55 ... +80 °C | |
| Main circuit | ||
| number of poles for main current circuit | 3 | |
| number of NO contacts for main contacts | 3 | |
| number of NC contacts for main contacts | 0 | |
| operating voltage | ||
| ● at AC-3 rated value maximum | 690 V | |
| ● at AC-3e rated value maximum | 690 V | |
| operational current | ||
| ● at AC-1 up to 690 V | ||
| — at ambient temperature 40 °C rated value | 40 A | |
| — at ambient temperature 60 °C rated value | 35 A | |
| ● at AC-3 | ||
| — at 400 V rated value | 9 A | |
| — at 690 V rated value | 9 A | |
| ● at AC-3e | ||
| — at 400 V rated value | 9 A | |
| — at 690 V rated value | 9 A | |
| connectable conductor cross-section in main circuit at AC-1 | ||
| ● at 60 °C minimum permissible | 10 mm² | |
| ● at 40 °C minimum permissible | 10 mm² | |
| operational current for approx. 200000 operating cycles at AC-4 | ||
| ● at 400 V rated value | 4.1 A | |
| ● at 690 V rated value | 3.3 A | |
| operating power | ||
| ● at AC-1 | ||
| — at 230 V rated value | 13.3 kW | |
| — at 230 V at 60 °C rated value | 13.3 kW | |
| — at 400 V at 60 °C rated value | 23 kW | |
| — at 690 V at 60 °C rated value | 40 kW | |
| ● at AC-3 | ||
| — at 230 V rated value | 2.2 kW | |
| — at 400 V rated value | 4 kW | |
| — at 690 V rated value | 7.5 kW | |
| ● at AC-3e | ||
| — at 230 V rated value | 2.2 kW | |
| — at 400 V rated value | 4 kW | |
| — at 690 V rated value | 7.5 kW | |
| operating power for approx. 200000 operating cycles at AC-4 | ||
| ● at 400 V rated value | 2 kW | |
| ● at 690 V rated value | 2.5 kW | |
| no-load switching frequency | ||
| ● at AC | 5 000 1/h | |
| operating frequency | ||
| ● at AC-1 maximum | 1 000 1/h | |
| ● at AC-3 maximum | 1 000 1/h | |
| ● at AC-3e maximum | 1 000 1/h | |
| ● at AC-4 maximum | 300 1/h | |
| Control circuit/ Control | ||
| type of voltage of the control supply voltage | AC | |
| control supply voltage at AC | ||
| ● at 50 Hz rated value | 230 V | |
| operating range factor control supply voltage rated value of magnet coil at AC | ||
| ● at 50 Hz | 0.8 ... 1.1 | |
| apparent pick-up power of magnet coil at AC | ||
| ● at 50 Hz | 65 VA | |
| inductive power factor with closing power of the coil | ||
| ● at 50 Hz | 0.82 | |
| apparent holding power of magnet coil at AC | ||
| ● at 50 Hz | 7.6 VA | |
| inductive power factor with the holding power of the coil | ||
| ● at 50 Hz | 0.25 | |
| Auxiliary circuit | ||
| number of NC contacts for auxiliary contacts instantaneous contact | 1 | |
| number of NO contacts for auxiliary contacts instantaneous contact | 1 | |
| operational current at AC-12 maximum | 10 A | |
| operational current at AC-15 | ||
| ● at 230 V rated value | 10 A | |
| ● at 400 V rated value | 3 A | |
| ● at 690 V rated value | 1 A | |
| operational current at DC-12 | ||
| ● at 24 V rated value | 6 A | |
| ● at 110 V rated value | 3 A | |
| ● at 220 V rated value | 1 A | |
| operational current at DC-13 | ||
| ● at 24 V rated value | 6 A | |
| ● at 110 V rated value | 1 A | |
| ● at 220 V rated value | 0.3 A | |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) | |
| UL/CSA ratings | ||
| yielded mechanical performance [hp] for 3-phase AC motor at 460/480 V rated value | 5 hp | |
| Short-circuit protection | ||
| design of the fuse link | ||
| ● for short-circuit protection of the main circuit | ||
| — with type of coordination 1 required | gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 63 A | |
| — with type of coordination 2 required | gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 25 A | |
| ● for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A | |
| Installation/ mounting/ dimensions | ||
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface | |
| fastening method side-by-side mounting | Yes | |
| fastening method | screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022 | |
| height | 85 mm | |
| width | 45 mm | |
| depth | 97 mm | |
| required spacing | ||
| ● with side-by-side mounting | ||
| — at the side | 0 mm | |
| Connections/ Terminals | ||
| type of electrical connection | ||
| ● for main current circuit | screw-type terminals | |
| ● for auxiliary and control circuit | screw-type terminals | |
| type of connectable conductor cross-sections for main contacts | ||
| ● solid or stranded | 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²) | |
| ● finely stranded with core end processing | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm² | |
| type of connectable conductor cross-sections | ||
| ● for auxiliary contacts | ||
| — solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) | |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) | |
| ● for AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) | |
| Safety related data | ||
| product function mirror contact according to IEC 60947-4-1 | Yes | |
| Electrical Safety | ||
| protection class IP on the front according to IEC 60529 | IP20 | |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front | |