Circuit breaker size S0 for motor protection, CLASS 10 A-release 27...32 A N-release 400 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC

Circuit breaker size S0 for motor protection, CLASS 10 A-release 27...32 A N-release 400 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC


Specifications
SKU
3RV2021-4EA15
Details

product brand name SIRIUS
product designation Circuit breaker
design of the product For motor protection
product type designation 3RV2
General technical data
size of the circuit-breaker S0
size of contactor can be combined company-specific S00, S0
product extension auxiliary switch Yes
power loss [W] for rated value of the current  
● at AC in hot operating state 13.25 W
● at AC in hot operating state per pole 4.4 W
insulation voltage with degree of pollution 3 at AC rated value 690 V
surge voltage resistance rated value 6 kV
shock resistance according to IEC 60068-2-27 25g / 11 ms
mechanical service life (operating cycles)  
● of the main contacts typical 100 000
● of auxiliary contacts typical 100 000
electrical endurance (operating cycles) typical 100 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 10/01/2009
SVHC substance name Lead - 7439-92-1
Lead titanium zirconium oxide - 12626-81-2
Weight 0.395 kg
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature  
● during operation -20 ... +60 °C
● during storage -50 ... +80 °C
● during transport -50 ... +80 °C
relative humidity during operation 10 ... 95 %
Environmental footprint
Environmental Product Declaration(EPD) Yes
global warming potential [CO2 eq] total 75.078 kg
global warming potential [CO2 eq] during manufacturing 2.68 kg
global warming potential [CO2 eq] during sales 0.143 kg
global warming potential [CO2 eq] during operation 72.7 kg
global warming potential [CO2 eq] after end of life -0.445 kg
Siemens Eco Profile (SEP) Siemens EcoTech
Main circuit
number of poles for main current circuit 3
adjustable current response value current of the current-dependent overload release 27 ... 32 A
type of voltage for main current circuit AC
operating voltage  
● rated value 20 ... 690 V
● at AC-3 rated value maximum 690 V
● at AC-3e rated value maximum 690 V
operating frequency rated value 50 ... 60 Hz
operational current rated value 32 A
operational current  
● at AC-3 at 400 V rated value 32 A
● at AC-3e at 400 V rated value 32 A
operating power  
● at AC-3  
— at 230 V rated value 7.5 kW
— at 400 V rated value 15 kW
— at 500 V rated value 18.5 kW
— at 690 V rated value 30 kW
● at AC-3e  
— at 230 V rated value 7.5 kW
— at 400 V rated value 15 kW
— at 500 V rated value 18.5 kW
— at 690 V rated value 30 kW
operating frequency  
● at AC-3 maximum 15 1/h
● at AC-3e maximum 15 1/h
Auxiliary circuit
design of the auxiliary switch transverse
type of voltage for auxiliary and control circuit AC/DC
number of NC contacts for auxiliary contacts 1
number of NO contacts for auxiliary contacts 1
number of CO contacts for auxiliary contacts 0
operational current of auxiliary contacts at AC-15  
● at 24 V 2 A
● at 120 V 0.5 A
● at 125 V 0.5 A
● at 230 V 0.5 A
operational current of auxiliary contacts at DC-13  
● at 24 V 1 A
● at 60 V 0.15 A
Protective and monitoring functions
product function  
● ground fault detection No
● phase failure detection Yes
trip class CLASS 10
design of the overload release thermal
maximum short-circuit current breaking capacity (Icu)  
● at AC at 240 V rated value 100 kA
● at AC at 400 V rated value 55 kA
● at AC at 500 V rated value 10 kA
● at AC at 690 V rated value 4 kA
operating short-circuit current breaking capacity (Ics) at AC  
● at 240 V rated value 100 kA
● at 400 V rated value 25 kA
● at 500 V rated value 5 kA
● at 690 V rated value 2 kA
response value current of instantaneous short-circuit trip unit 400 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor  
● at 480 V rated value 32 A
● at 600 V rated value 32 A
yielded mechanical performance [hp]  
● for single-phase AC motor  
— at 110/120 V rated value 2 hp
— at 230 V rated value 5 hp
● for 3-phase AC motor  
— at 200/208 V rated value 7.5 hp
— at 220/230 V rated value 10 hp
— at 460/480 V rated value 20 hp
contact rating of auxiliary contacts according to UL C300 / R300
Short-circuit protection
product function short circuit protection Yes
design of the short-circuit trip magnetic
design of the fuse link  
● for short-circuit protection of the auxiliary switch required Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)
design of the fuse link for IT network for short-circuit protection of the main circuit  
● at 400 V gL/gG 63 A
● at 500 V gL/gG 63 A
● at 690 V gL/gG 63 A
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height 97 mm
width 45 mm
depth 97 mm
required spacing  
● with side-by-side mounting at the side 0 mm
● for grounded parts at 400 V  
— downwards 30 mm
— upwards 30 mm
— at the side 9 mm
● for live parts at 400 V  
— downwards 30 mm
— upwards 30 mm
— at the side 9 mm
● for grounded parts at 500 V  
— downwards 30 mm
— upwards 30 mm
— at the side 9 mm
● for live parts at 500 V  
— downwards 30 mm
— upwards 30 mm
— at the side 9 mm
● for grounded parts at 690 V  
— downwards 50 mm
— upwards 50 mm
— backwards 0 mm
— at the side 30 mm
— forwards 0 mm
● for live parts at 690 V  
— downwards 50 mm
— upwards 50 mm
— backwards 0 mm
— at the side 30 mm
— forwards 0 mm
Connections/ Terminals
type of electrical connection  
● for main current circuit screw-type terminals
● for auxiliary and control circuit screw-type terminals
arrangement of electrical connectors for main current circuit Top and bottom
type of connectable conductor cross-sections  
● for main contacts  
— solid or stranded 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
— finely stranded with core end processing 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
● for AWG cables for main contacts 2x (16 ... 12), 2x (14 ... 8)
type of connectable conductor cross-sections  
● for auxiliary contacts  
— solid or stranded 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14)
tightening torque  
● for main contacts with screw-type terminals 2 ... 2.5 N·m
● for auxiliary contacts with screw-type terminals 0.8 ... 1.2 N·m
design of screwdriver shaft Diameter 5 to 6 mm
size of the screwdriver tip Pozidriv size 2
design of the thread of the connection screw  
● for main contacts M4
● of the auxiliary and control contacts M3
Safety related data
product function suitable for safety function Yes
suitability for use  
● safety-related switching on No
● safety-related switching OFF Yes
service life maximum 10 a
test wear-related service life necessary Yes
proportion of dangerous failures  
● with low demand rate according to SN 31920 40 %
● with high demand rate according to SN 31920 50 %
B10 value with high demand rate according to SN 31920 5 000
failure rate [FIT] with low demand rate according to SN 31920 50 FIT
ISO 13849
device type according to ISO 13849-1 3
overdimensioning according to ISO 13849-2 necessary Yes
IEC 61508
safety device type according to IEC 61508-2 Type A
T1 value  
● for proof test interval or service life according to IEC 61508 10 a
Electrical Safety
protection class IP on the front according to IEC 60529 IP20
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front
Display
display version for switching status Handle

View more about Circuit breaker size S0 for motor protection, CLASS 10 A-release 27...32 A N-release 400 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC on main site