SIMATIC ET 200SP, digital input module, DI 8x 24 V DC High Feature, input type 3 (IEC 61131), sink input, (PNP, sink input) Packing unit: 1 unit, suitable for BU type A0, color code CC01, input delay 0.05..20 ms; Channel diagnostics for: Encoder power supply short circuit, wire break, supply voltage, channel fault LED
Category: SIEMENS Simatic Control Systems
Specifications
SKU
6ES7131-6BF00-0CA0
Details
| General information | ||
| Product type designation | DI 8x24 V DC HF | |
| HW functional status | From FS07 | |
| Firmware version | ||
| ● FW update possible | Yes | |
| usable BaseUnits | BU type A0 | |
| Color code for module-specific color identification plate | CC01 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| ● Isochronous mode | Yes; 250 µs | |
| ● suitable for operation on PROFINET R1 IMs | Yes | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - | |
| ● STEP 7 configurable/integrated from version | V5.5 / - | |
| ● PCS 7 configurable/integrated from version | V8.1 SP1 | |
| ● PCS neo can be configured/integrated from version | from V1.0.0 | |
| ● PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher | |
| ● PROFINET from GSD version/GSD revision | GSDML V2.3 | |
| Operating mode | ||
| ● DI | Yes | |
| ● Counter | No | |
| ● Oversampling | No | |
| ● MSI | Yes | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Input current | ||
| Current consumption (rated value) | 20 mA | |
| Current consumption, max. | 39 mA | |
| Encoder supply | ||
| Number of outputs | 8 | |
| Output voltage, min. | 19.2 V | |
| Short-circuit protection | Yes | |
| 24 V encoder supply | ||
| ● 24 V | Yes | |
| ● Short-circuit protection | Yes; per channel, electronic | |
| ● Output current per channel, max. | 700 mA | |
| ● Output current per module, max. | 700 mA | |
| Power loss | ||
| Power loss, typ. | 1.5 W; 24 V, 8 inputs supplied via encoder supply | |
| Address area | ||
| Address space per module | ||
| ● Inputs | 1 byte; + 1 byte for QI information | |
| Hardware configuration | ||
| Automatic encoding | Yes | |
| ● Mechanical coding element | Yes | |
| ● Type of mechanical coding element | Type A | |
| Submodules | ||
| ● Number of configurable submodules, max. | 4 | |
| Selection of BaseUnit for connection variants | ||
| ● 1-wire connection | BU type A0 | |
| ● 2-wire connection | BU type A0 | |
| ● 3-wire connection | BU type A0 with AUX terminals or potential distributor module | |
| ● 4-wire connection | BU type A0 + Potential distributor module | |
| Digital inputs | ||
| Number of digital inputs | 8 | |
| Digital inputs, parameterizable | Yes | |
| Source/sink input | P-reading | |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
| Pulse extension | Yes; Pulse duration from 4 µs | |
| ● Length | 2 s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s | |
| Edge evaluation | Yes; rising edge, falling edge, edge change | |
| Input voltage | ||
| ● Rated value (DC) | 24 V | |
| ● for signal "0" | -30 to +5 V | |
| ● for signal "1" | +11 to +30V | |
| Input current | ||
| ● for signal "1", typ. | 2.5 mA | |
| Input delay (for rated value of input voltage) | ||
| for standard inputs | ||
| — parameterizable | Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) | |
| — at "0" to "1", min. | 0.05 ms | |
| — at "0" to "1", max. | 20 ms | |
| — at "1" to "0", min. | 0.05 ms | |
| — at "1" to "0", max. | 20 ms | |
| Cable length | ||
| ● shielded, max. | 1 000 m | |
| ● unshielded, max. | 600 m | |
| Encoder | ||
| Connectable encoders | ||
| ● 2-wire sensor | Yes | |
| — permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
| Isochronous mode | ||
| Filtering and processing time (TCI), min. | 420 µs | |
| Bus cycle time (TDP), min. | 500 µs | |
| Jitter, max. | 8 µs | |
| Interrupts/diagnostics/status information | ||
| Diagnostics function | Yes | |
| Alarms | ||
| ● Diagnostic alarm | Yes; channel by channel | |
| ● Hardware interrupt | Yes; Parameterizable, channels 0 to 7 | |
| Diagnoses | ||
| ● Diagnostic information readable | Yes | |
| ● Monitoring the supply voltage | Yes | |
| — parameterizable | Yes | |
| ● Monitoring of encoder power supply | Yes; channel by channel | |
| ● Wire-break | Yes; Channel by channel, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm | |
| ● Short-circuit | Yes; channel by channel | |
| Diagnostics indication LED | ||
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
| ● Channel status display | Yes; green LED | |
| ● for channel diagnostics | Yes; red LED | |
| ● for module diagnostics | Yes; green/red DIAG LED | |
| Potential separation | ||
| Potential separation channels | ||
| ● between the channels | No | |
| ● between the channels and backplane bus | Yes | |
| ● between the channels and the power supply of the electronics | No | |
| Isolation | ||
| Isolation tested with | 707 V DC (type test) | |
| Standards, approvals, certificates | ||
| Suitable for safety functions | No | |
| Ecological footprint | ||
| ● environmental product declaration | Yes | |
| Global warming potential | ||
| — global warming potential, (total) [CO2 eq] | 15.9 kg | |
| — global warming potential, (during production) [CO2 eq] | 3.69 kg | |
| — global warming potential, (during operation) [CO2 eq] | 12.7 kg | |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.495 kg | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | -30 °C; < 0 °C as of FS07 | |
| ● horizontal installation, max. | 60 °C | |
| ● vertical installation, min. | -30 °C; < 0 °C as of FS07 | |
| ● vertical installation, max. | 50 °C | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | |
| Dimensions | ||
| Width | 15 mm | |
| Height | 73 mm | |
| Depth | 58 mm | |
| Weights | ||
| Weight, approx. | 28 g | |
View more about SIMATIC ET 200SP, digital input module, DI 8x 24 V DC High Feature, input type 3 (IEC 61131), sink input, (PNP, sink input) Packing unit: 1 unit, suitable for BU type A0, color code CC01, input delay 0.05..20 ms; Channel diagnostics for: Encoder power supply short circuit, wire break, supply voltage, channel fault LED on main site