SIMATIC ET 200SP, Digital input module, DI 16x 24V DC Standard, type 3 (IEC 61131), sink input, (PNP, P-reading), Packing unit: 1 Piece, fits to BU-type A0, Colour Code CC00, input delay time 0,05..20ms, diagnostics wire break, diagnostics supply voltage

SIMATIC ET 200SP, Digital input module, DI 16x 24V DC Standard, type 3 (IEC 61131), sink input, (PNP, P-reading), Packing unit: 1 Piece, fits to BU-type A0, Colour Code CC00, input delay time 0,05..20ms, diagnostics wire break, diagnostics supply voltage


Specifications
SKU
6ES7131-6BH01-0BA0
Details

General information
Product type designation DI 16x24VDC ST
HW functional status From FS02
Firmware version V0.0
● FW update possible No
usable BaseUnits BU type A0
Color code for module-specific color identification plate CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● suitable for operation on PROFINET R1 IMs Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14
● STEP 7 configurable/integrated from version V5.5 SP3
● PCS 7 configurable/integrated from version V8.1 SP1
● PCS neo can be configured/integrated from version from V1.0.0
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● DI Yes
● Counter No
● Oversampling No
● MSI No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 90 mA
Encoder supply
24 V encoder supply
● 24 V No
Power loss
Power loss, typ. 1.7 W
Address area
Address space per module
● Inputs 2 byte; + 2 bytes for QI information
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0 + Potential distributor module
● 3-wire connection BU type A0 + Potential distributor module
● 4-wire connection BU type A0 + Potential distributor module
Digital inputs
Number of digital inputs 16
Digital inputs, parameterizable Yes
Source/sink input P-reading
Input characteristic curve in accordance with IEC 61131, type 3 Yes
Input voltage
● Rated value (DC) 24 V
● for signal "0" -30 to +5 V
● for signal "1" +11 to +30V
Input current
● for signal "1", typ. 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length)
— at "0" to "1", min. 0.05 ms
— at "0" to "1", max. 20 ms
— at "1" to "0", min. 0.05 ms
— at "1" to "0", max. 20 ms
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Diagnostic information readable Yes
● Monitoring the supply voltage Yes
— parameterizable Yes
● Monitoring of encoder power supply No
● Wire-break Yes; Module-by-module, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm
● Short-circuit No
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics No
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 21 kg
— global warming potential, (during production) [CO2 eq] 4.25 kg
— global warming potential, (during operation) [CO2 eq] 17.5 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.743 kg
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; < 0 °C as of FS02
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; < 0 °C as of FS02
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 28 g

View more about SIMATIC ET 200SP, Digital input module, DI 16x 24V DC Standard, type 3 (IEC 61131), sink input, (PNP, P-reading), Packing unit: 1 Piece, fits to BU-type A0, Colour Code CC00, input delay time 0,05..20ms, diagnostics wire break, diagnostics supply voltage on main site